Pressure transmitter TST-K20
Measuring ranges from -1 ... 0 bar to 0 ... +20 bar
Also as intrinsically safe version with ATEX-approval
Frontflush, dry ceramic measuring cell
Vacuum-proof and high overload resistance
Total measurement error ≤ 0.3 % FS
product description Pressure transmitter TST-K20
The TST-K20 pressure transmitters are equipped with a flush-mounted process connection with G 1/2 "external thread and a vacuum-resistant, dry ceramic measuring cell. TST-K20 pressure transmitters are especially suitable for the measuring of pressure in viscous media or liquids containing suspended solids or particles. The measuring range can be freely calibrated from -1 ... 0 bar up to 0 ... +20 bar and is characterized by a very high overload resistance. The permissible media temperature is -25 ... +100 °C, the measured value is displayed as a 4 ... 20 mA (2-wire) analog output signal. Measuring ranges ≥ 100 mbar are optionally also available with Ex approval (acc. to I M2 EEx ia I / II 1G EEx ia IIC T4 / T6).
Standard pressure ranges TST-K20 for gauge pressure measurement Individual pressure ranges on request |
||||||||
Measuring range | P(mbar) | 60* | 100 | 160 | 200 | 250 | 400 | 500 |
Overpressure | P(bar) | -0,3 / +4 | -0,3 / +4 | -0,3 / +4 | -0,3 / +4 | -0,3 / +4 | -1 / +6 | -1 / +6 |
Measuring range | P(bar) | 0,6 | 1,0 | 1,6 | 2,0 | 2,5 | 4,0 | 5,0 |
Overpressure | P(bar) | -1 / +10 | -1 / +10 | -1 / +15 | -1 / +15 | -1 / +15 | -1 / +25 | -1 /+40 |
Measuring range | P(bar) | 6,0 | 10 | 16 | 20 | -1 ... +1 | ||
Overpressure | P(bar) | -1 / +40 | -1 / +40 | -1 / +40 | -1 / +40 | -1 / +10 |
* the total measurement error for this measuring range is ≤± 0.5 % FS
Technical data | Pressure transmitter TST-K20 |
|
Electrical parameters | ||
Output signal Operating voltage UB Permitted max. load RA |
4 ... 20 mA (2-wire) 9 ... 30 V DC RA ≤ (UB - 9 V) / 20 mA |
|
Response time (10 ... 90 %) | < 200 ms | |
Accuracy specifications | ||
Total error at RT |
≤± 0.30 % FS - including nonlinearity, hysteresis, zero point and full scale error (according to IEC 61298-2). |
|
Stability per year | ≤± 0.3 % FS |