Level limit controller TS-KGS-W1222
Available for 2-wire or 3-wire level limit switches such as TS-KGS-25
Two independent relay outputs
Preconfigured program for pump control
Integrated power supply unit to supply the connected sensors with 12 V DC
product description Level limit controller TS-KGS-W1222
- Available for 2-wire or 3-wire level limit switches such as TS-KGS-25
- Special design for 2-wire level limit switches with additional programming wire such as TS-KGS
- Two independent relay outputs
- Preconfigured program for pump control
- Integrated power supply unit to supply the connected sensors with 12 V DC
- Optical status indication
- Simple handling and installation
- IP 65 housing, designed for wall mounting
The level limit controller TS-KGS-W1222 is designed for the evaluation of 2-wire or 3-wire level limit switches. For 2-wire level limit switches with additional programming wire, such as TS-KGS, a special design for simplified sensor configuration is available. The level limit controller provides a supply voltage of 12 V DC for the sensors and controls two independent Relay outputs. The TS-KGS-W1222 is standard equipped with a preconfigured program for pump control (monitoring of a liquid level between minimum and maximum), which can be enabled by a DIP switch.
Technical data type TS-KGS-W1222 |
|
Operating Voltage UB | 230 V (50 Hz) ±10 % |
Nominal power demand | 4 VA |
Sensor supply voltage | 12 V DC ±10 % |
Maximum output current (including inputs IN1, IN2) | 50 mA |
No. of level limit sensors | 1 oder 2 |
No. of relay outputs | 2 |
Relay output type | 250 V AC, 2 A, 500 VA |
Max. switching frequency at maximum load | 360 / h |
Ambient temperature range | -20 … +50 °C |
Max. / recommended conductor size | Max. 2,5 mm2 / 0,14 … 0,5 mm2 |
Housing material | ABS + Fiberglas |
Protection class | IP 65 |
Weight | ~ 350 g |
Electrical safety and electromagnetic compatibility: The level limit controller TS-KGS-W1222 is equipped with an overload protection. The control is protected by a fuse type T 50 mA. Certified electrical safety and CE conformity according to directive: EN 61010-1. Electromagnetic compatibility according to directive: EN55022, EN61000-4-2, -3, -4,-5, -6 und EN 6100-6-2. |