Universal isolation amplifier TV 500-Ex and Universal Ex seperator ST 500-Ex
Universal Ex seperator with internal supply for 2- and 3-wire sensors
Universal inputs 0/4 ... 20 mA and 0/2 ... 10 V DC, intrinsically safe acc. ATEX II (1) G [Ex ia] IIC and ATEX II (1) D [Ex iaD]
Outputs 0/4 ... 20 mA simultaneously 0/2 ... 10 V DC
Galvanic isolation between input / output / supply voltage
22.5 mm standard housing for DIN rail mounting
product description Universal isolation amplifier TV 500-Ex and Universal Ex seperator ST 500-Ex
- Universal inputs 0/4 ... 20 mA and 0/2 ... 10 V DC, intrinsically safe acc. ATEX II (1) G [Ex ia] IIC and ATEX II (1) D [Ex iaD]
- Outputs 0/4 ... 20 mA simultaneously 0/2 ... 10 V DC
- Supply voltage 85 ... 253 V AC or 10 ... 30 V AC / DC
- Galvanic isolation between input / output / supply voltage
- Integrated transmitter supply for 2- and 3-wire sensors (only separator ST500-Ex)
- Operating indication by LED
- 22.5 mm standard housing for DIN rail mounting
The universal isolation amplifiers of the TV500-Ex series are suitable for potential separation or for the conversion of standard signals from hazardous areas. The universal design of inputs and outputs and the two wide supply voltage ranges limit the variety of types to only two versions. The isolator ST500-Ex additionally allows the direct connection of active 2-wire sensors (4 ... 20 mA) and 3-wire sensors in hazardous areas.
Technical data |
Type: TV 500-Ex / ST 500-Ex |
||||
Explosion protection Approval Marking U0 I0
P0
|
TÜV 97 ATEX 1150, 2nd supplement II (1) G [Ex ia] IIC, II (1) D [Ex iaD] 25,2 V TV 500-Ex : 1 mA ST 500-Ex : 95 mA TV 500-Ex : < 1 mW (characteristic linear) ST 500-Ex : 600 mW (characteristic linear) |
||||
Type of protection Ex ia |
IIC |
IIB |
|||
L0
|
TV 500-Ex ST 500-Ex |
100 mH 2 mH |
0,5 mH 0,2 mH |
100 mH 15 mH |
0,5 mH 1 mH |
C0
|
TV 500-Ex ST 500-Ex |
84 nF 47 nF |
100 nF 107 nF |
460 nF 370 nF |
570 nF 430 nF |
The effective internal capacitances Ci and inductances Li are negligibly small. |
|||||
The intrinsically safe measuring inputs are safely galvanically isolated from all other circuits up to a peak value of 375 V. |
|||||
Measuring inputs Current input Voltage input Span and initial value 4 mA/2 V |
0/4 ... 20 mA switchable, Ri = 25 Ω, max. 100 mA overload 0/2 ... 10 V DC switchable, Ri ca. 40 kΩ, max. 100 V overload ca. ±20 % adjustabel |
||||
Transmitter supply Short circit (cl. 1 and 2) |
approx. 20 V DC, Ri approx. 300 Ω (ST 500-Ex only) Output current < 27 mA |
||||
Outputs Current output Voltage output
Rated voltage
Recovery time (T90) Basic accuracy Temperature drift Repeatability Power supply effect |
0/4 ... 20 mA switchable, burden max. 1 kΩ 0/2 ... 10 V DC switchable Load max. 15 mA, short-circuit proof (simultaneous with current output max. 5 mA) 253 V AC or rather. 125 V DC (Um) acc. to EN 60079-0 Max. Short-circuit current of the connected equipment 2 A < 100 ms < 0,3 % < 0,01 % / K < 0,1 % < 0,1 % |
||||
Behavior of the current output at sensor error in the configuration 4 ... 20 mA (for input and output) |
|||||
Input |
Short circuit cl. 1, 2 |
Short circuit cl. 2, 3 |
Interrruption |
Blasting (max. 100 mA) |
|
TV 500-Ex |
23 ... 27 mA < 2,5 mA |
< 2,5 mA |
< 2,5 mA |
Limit value 23 ... 27 mA |
|
ST 500-Ex |
100 mH |
< 2,5 mA |
< 2,5 mA |
Limit value 23 ... 27 mA |
|
Housing Design Weight Protection class Connection type Mounting position |
Housing for DIN-rail mounting, out of Makrolon 8020 UL94V-1 ~ 200 g Housing IP30, screw terminalIP20, (BGV A3) Screw terminals with wire protection, max. 2,5 mm² Installation in a dry, clean and well-supervised environment acc. to DIN EN60079-11:2007, para. 6.1 |